@article{oai:nagasaki-u.repo.nii.ac.jp:00001085, author = {Yamashita, Takahiko and Iwanaga, Kazuhisa and Furusato, Tomohiro and Asari, Naoki and Sato, Junichi}, issue = {5}, journal = {IEEE Transactions on Dielectrics and Electrical Insulation}, month = {Oct}, note = {Solid insulated switchgear (SIS) has been developed as a substitution for medium voltage SF6 gas insulated switchgear. Its main circuits including a vacuum interrupter are coated with epoxy resin and a solid/gas insulation system is formed. For further miniaturization and higher stress design, the authors investigated the surface insulation performance of the solid/gas insulation system containing an embedded electrode. In the previous study, the authors investigated the surface breakdown characteristics. The authors also investigated the surface discharge propagation characteristics and proposed an estimation method of the surface breakdown voltage. In the present study, the authors investigated the surface breakdown characteristics numerically. The calculation was done based on the estimation method proposed previously. The divided voltage ratio, the radius of the embedded electrode, the enhancement factor of the surface insulation strength and the peak value of the surface breakdown voltage are examined. As a result, the characteristics of the parameters and the criteria for the optimum insulation design were clarified., IEEE Transactions on Dielectrics and Electrical Insulation, 24(5), pp.3055-3062; 2017}, pages = {3055--3062}, title = {Basic study on surface insulation design of solid/gas composite insulation system with embedded electrode}, volume = {24}, year = {2017} }